Permit: T18FC00440
Permit Details
Apply Date:
05/29/2018
Applicant:
WESTERN STATES FIRE PROTECTION C **APA**
Description:
INSTALL NEW FIRE PROTECTION SYSTEMS.
Contractors:
- WESTERN STATES FIRE PROTECTION C **APA**
Completed Inspections
Permit Status: Final
Permit Number: T18FC00440
Permit Description: INSTALL NEW FIRE PROTECTION SYSTEMS.
Total Completed Inspections - 3
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
12/14/2018 | FIRE SPKLR - OH PIPING & HYDRO | jvincent | Approved | |
12/14/2018 | FIRE SPKLR - OH PIPING & HYDRO | jvincent | Approved | Hydro approved floor 1 with canopy |
12/19/2018 | FIRE SPKLR - FINAL | JPEELDAVIS | Approved | fire sprinkler final for the 3rd floor for TCO Need to add one head in the janitor closet Need to add one head on the TES war room # 3094 Flow was at 59 seconds Tamper confirmed on Need to do main drain at final Place caps on the standpipes |