Permit: T18FC00440

Parcel: 11620134B


Addresses:

875 W CUSHING ST


Inspection Status: Approved

Inspection History: FIRE SPKLR - FINAL

Permit Number - T18FC00440

Inspection Description - FIRE SPKLR - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
04/12/2019 FIRE SPKLR - FINAL Approved
03/19/2019 FIRE SPKLR - FINAL Partial Approval Everything from the list is complete. Need the fire riser room cleaned and all the ceiling tiles in place for final
01/14/2019 FIRE SPKLR - FINAL Partial Approval 2nd Floor
-Add 3 sprinkler heads under duct work.
-Add 1 head in room 2014.
12/19/2018 FIRE SPKLR - FINAL Partial Approval fire sprinkler final for the 3rd floor for TCO
Need to add one head in the janitor closet
Need to add one head on the TES war room # 3094
Flow was at 59 seconds
Tamper confirmed on
Need to do main drain at final
Place caps on the standpipes
12/14/2018 FIRE SPKLR - FINAL Partial Approval Walked floors 2 & 3. Partial Approval. Still need bell, all ceiling tiles installed and main drain test to final these floors.