Permit Details

Status:
Final
Type:
Fire Alarm & Detection Systems
Address:
875 W CUSHING ST
Apply Date:
03/21/2018
Applicant:
FIRETROL PROTECTION SYSTEMS INC
Description:
New Fire Alarm Install
Contractors:
  • FIRETROL PROTECTION SYSTEMS INC

Completed Inspections

Permit Status: Final
Permit Number: T18FC00237
Permit Description: New Fire Alarm Install
Total Completed Inspections - 1
Date Description Inspector Results Comments
12/19/2018 FIRE - ALARM FINAL JPEELDAVIS Approved 3rd floor fire alarm partial.
Verified the flow @ 59 seconds, confirmed the tamper switch
Need to add the tone to the voice
Need to add one notificaiton appliance in the call center
Will verify duct detector shut down at final for CofO and or TCO to occupy with people.