Inspection History Details
Inspection Status: Approved
Inspection History: FIRE - ALARM FINAL
Permit Number - T18FC00237
Inspection Description - FIRE - ALARM FINAL
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/11/2019 | FIRE - ALARM FINAL | Approved | Additional items from punch list have been tested and passed. There will be an intelligibility test at a later date once the building is occupied. We can leave the CM permit open for that test. | |
| 02/28/2019 | FIRE - ALARM FINAL | Partial Approval | Verified that the tone was added to the voice Verified that they added the 3rd floor notification device as requested. The need to add outside weatherproof notification to the East side patio Need to shut down the projector in the "movie" room on fire alarm Add extra notification to the main training room 1st floor Add extra notification to the NW area outside of ttraining area Need to install the remote annunciator and the remote voice control Add visual only to the FACP room |
|
| 12/19/2018 | FIRE - ALARM FINAL | Partial Approval | 3rd floor fire alarm partial. Verified the flow @ 59 seconds, confirmed the tamper switch Need to add the tone to the voice Need to add one notificaiton appliance in the call center Will verify duct detector shut down at final for CofO and or TCO to occupy with people. |