Automatic Fire Extingshing Sys - Installation of New Wet Automatic Fire Sprinkler System; Commercial Fire Pumps and Related Equipment - New Pumps: 1
Completed Inspections
Permit Status: Expired
Permit Number: T18FC00085
Permit Description: Automatic Fire Extingshing Sys - Installation of New Wet Automatic Fire Sprinkler System; Commercial Fire Pumps and Related Equipment - New Pumps: 1
Total Completed Inspections - 1
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
10/30/2018 | COT - FCON - Pump - Final | Passed | {Activity date: 10/30/2018; Status: Approved; Inspector: JPEELDAVIS; Comment: Entered by JPEELDA1 - } ; {Activity date: 10/02/2018; Status: Partial Approval; Inspector: JPEELDAVIS; Comment: Entered by JPEELDA1 - Need to re-wire the electric to the pump Pump suction was at 20psi but the curve passed Need to connect to the fire alarm system Need to re-test the fire pump once complete Test broke the double back flow preventer so that will need to be tested Need to open the closed street control valve} |