Permit: T18FC00085

Parcel: 14043013B

Inspection Status: Passed

Inspection History: COT - FCON - Pump - Final

Date Description Inspector Results Comments
10/30/2018 COT - FCON - Pump - Final JPEELDAVIS Approved Entered by JPEELDA1 -
10/02/2018 COT - FCON - Pump - Final JPEELDAVIS Partial Approval Entered by JPEELDA1 - Need to re-wire the electric to the pump Pump suction was at 20psi but the curve passed Need to connect to the fire alarm system Need to re-test the fire pump once complete Test broke the double back flow preventer so that will need to be tested Need to open the closed street control valve