Apply Date:
01/19/2018
Applicant:
KELLOGG FIRE N WIRE INC ,
Description:
New Fire Sprinkler System
Contractors:
- KELLOGG FIRE N WIRE INC ,
Completed Inspections
Permit Status: Final
Permit Number: T18FC00064
Permit Description: New Fire Sprinkler System
Total Completed Inspections - 3
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
11/29/2018 | FIRE SPKLR - OH PIPING & HYDRO | JPEELDAVIS | Approved | |
11/29/2018 | FIRE SPKLR - OH PIPING & HYDRO | JPEELDAVIS | Approved | Basement and 4th floor ok 200 psi |
12/20/2018 | FIRE SPKLR - FINAL | JPEELDAVIS | Approved | Outside Room 411 needs to have 2 escutcheons in place Outside Room 411 escutheon needs painting and drywall completed Room 413 closet head is painted x 2 Room 414 2 heads capped and need escutcheon Room 414 bedroom closet head is painted Room 415 closet head has dry wall on it Room 416 linen closet head is painted Room 417 heads are taped and need escutcheons in place Room 408 closet front side head is painted Room 407 outside the front closet is painted, kitchen head needs dry wall, paint and ecutcheon Room 405 bathroom and closet head are painted. Both heads in the other bathroom are painted and need drywall corrected Room 305 hallway head needs drywall and is painted Room 311 head front entry is painted. Head located in the kitchen needs paint and drywall corrected Room 313 front entry head is too close to the wall need to move Room 314master bathroom closet head to close to the wall need to move Room 315 2 back bedroom heads back side of fans are painted Room 315 Kitchen light obsturcted needs to be lowered Room 316 kitchen light is obsturcted needs to be lowered Room 317 kitchen light is obstructing needs the head to be lowered Room 317Master bathroom head is painted Room 318 bathroom closet head is too close to the wall and needs to be moved Room 319 closet head is to close to the wall and needs to be moved Ceiling outside Rooom 219 heads are taped Room 218 Front enrtry head is painted Room 217 Master bathroom head is painted Living room head needs to have the drywall corrected. Front entry head is painted and needs to be replaced. Bedroom entry area head is painted and needs to be replaced Room 216Kitchen light is obstructing the head and it needs to be lowered Room 216 Front entry head is painted, closet by entry too close to the wall needs to be moved and is painted, back bedroom head is painted, small side closet painted head and back bathroom has a painted head Outside Room 215 head is taped Room 215 kitchen light is causing an obstruction head needs to be lowered, master bedroom head needs the drywall to be corrected, master bathroom closet head is painted, front entry head is painted, bedroom 1 closet head is taped and needs escutcheon, bedroom 2 closet and bathroom have heads that are painted Room 214 Entry to back bedroom capped off and in the bedroom needs trim and checked for paint Room 213 Small closet by the bedroom head is painted. Back bedroom head is capped and needs trim and checked for paint Room 210 closet head painted front entry Room 209 closet head is painted Room 208 closet head needs drywall, paint, kitchen head is obsturcted by the light and needs to be lowered Room 207 linen closet head is too clsoe to the wall and needs to be moved same with the laundry head Standpipes need to be capped. |