Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Details

Status:
Final
Type:
Automatic Fire Extingshing Sys
Apply Date:
01/19/2018
Applicant:
KELLOGG FIRE N WIRE INC ,
Description:
New Fire Sprinkler System
Contractors:
  • KELLOGG FIRE N WIRE INC ,

Completed Inspections

Permit Status: Final
Permit Number: T18FC00064
Permit Description: New Fire Sprinkler System
Total Completed Inspections - 3
Date Description Inspector Results Comments
11/29/2018 FIRE SPKLR - OH PIPING & HYDRO JPEELDAVIS Approved
11/29/2018 FIRE SPKLR - OH PIPING & HYDRO JPEELDAVIS Approved Basement and 4th floor ok 200 psi
12/20/2018 FIRE SPKLR - FINAL JPEELDAVIS Approved Outside Room 411 needs to have 2 escutcheons in place
Outside Room 411 escutheon needs painting and drywall completed
Room 413 closet head is painted x 2
Room 414 2 heads capped and need escutcheon
Room 414 bedroom closet head is painted
Room 415 closet head has dry wall on it
Room 416 linen closet head is painted
Room 417 heads are taped and need escutcheons in place
Room 408 closet front side head is painted
Room 407 outside the front closet is painted, kitchen head needs dry wall, paint and ecutcheon
Room 405 bathroom and closet head are painted. Both heads in the other bathroom are painted and need drywall corrected
Room 305 hallway head needs drywall and is painted
Room 311 head front entry is painted. Head located in the kitchen needs paint and drywall corrected
Room 313 front entry head is too close to the wall need to move
Room 314master bathroom closet head to close to the wall need to move
Room 315 2 back bedroom heads back side of fans are painted
Room 315 Kitchen light obsturcted needs to be lowered
Room 316 kitchen light is obsturcted needs to be lowered
Room 317 kitchen light is obstructing needs the head to be lowered
Room 317Master bathroom head is painted
Room 318 bathroom closet head is too close to the wall and needs to be moved
Room 319 closet head is to close to the wall and needs to be moved
Ceiling outside Rooom 219 heads are taped
Room 218 Front enrtry head is painted
Room 217 Master bathroom head is painted Living room head needs to have the drywall corrected. Front entry head is painted and needs to be replaced. Bedroom entry area head is painted and needs to be replaced
Room 216Kitchen light is obstructing the head and it needs to be lowered
Room 216 Front entry head is painted, closet by entry too close to the wall needs to be moved and is painted, back bedroom head is painted, small side closet painted head and back bathroom has a painted head
Outside Room 215 head is taped
Room 215 kitchen light is causing an obstruction head needs to be lowered, master bedroom head needs the drywall to be corrected, master bathroom closet head is painted, front entry head is painted, bedroom 1 closet head is taped and needs escutcheon, bedroom 2 closet and bathroom have heads that are painted
Room 214 Entry to back bedroom capped off and in the bedroom needs trim and checked for paint
Room 213 Small closet by the bedroom head is painted. Back bedroom head is capped and needs trim and checked for paint
Room 210 closet head painted front entry
Room 209 closet head is painted
Room 208 closet head needs drywall, paint, kitchen head is obsturcted by the light and needs to be lowered
Room 207 linen closet head is too clsoe to the wall and needs to be moved same with the laundry head
Standpipes need to be capped.

Documents

File Name Document Type  
001_FP1.TIF FIRE PLANS VIEW
002_FP2.TIF FIRE PLANS VIEW
003_FP3.TIF FIRE PLANS VIEW
004_FP4.TIF FIRE PLANS VIEW
005_FP5.TIF FIRE PLANS VIEW
006_FP6.TIF FIRE PLANS VIEW
007_FP7.TIF FIRE PLANS VIEW
008_FP8.TIF FIRE PLANS VIEW
009_FP9.TIF FIRE PLANS VIEW
010_FP10.TIF FIRE PLANS VIEW
011_FP11.TIF FIRE PLANS VIEW
012_FP12.TIF FIRE PLANS VIEW
None DOCUMENTS VIEW