Permit: T18FC00064

Parcel: 11620633B


Addresses:

855 W CONGRESS ST

Inspection Status: Partial Approval

Inspection History: FIRE SPKLR - OH PIPING & HYDRO

Date Description Inspector Results Comments
11/29/2018 FIRE SPKLR - OH PIPING & HYDRO Partial Approval Basement and 4th floor ok 200 psi
11/29/2018 FIRE SPKLR - OH PIPING & HYDRO Approved
10/04/2018 FIRE SPKLR - OH PIPING & HYDRO Partial Approval 1st floor east side offices 205 psi
08/14/2018 FIRE SPKLR - OH PIPING & HYDRO Partial Approval 210 psi for the third floor. Ok to dry wall
07/23/2018 FIRE SPKLR - OH PIPING & HYDRO Partial Approval 200 psi 2nd floor only fees will be added for all inspections this one and going forward/
06/25/2018 FIRE SPKLR - OH PIPING & HYDRO Partial Approval 200 psi for all three risers on the 1st floor only
06/15/2018 FIRE SPKLR - OH PIPING & HYDRO Cancelled