Permit: T17FC00507
Permit Details
Apply Date:
06/19/2017
Applicant:
N/A
Description:
INSTALL NEW FIRE SPRINKLER SYSTEM THROUGHOUT THE BUILDING & GARAGE.
Contractors:
- MAXIMUM FIRE PROTECTION L L C ** APA **
Completed Inspections
Permit Status: Final
Permit Number: T17FC00507
Permit Description: INSTALL NEW FIRE SPRINKLER SYSTEM THROUGHOUT THE BUILDING & GARAGE.
Total Completed Inspections - 2
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/17/2017 | FIRE SPKLR - OH PIPING & HYDRO | JPEELDAVIS | Approved | All areas were completed. Need to add two heads in the NW room bedroom and living room |
| 12/28/2017 | FIRE SPKLR - FINAL | jvincent | Approved | PA only on room #102 and the hallway/corridor that serves that room. This was only done so they could get TCO. Main drain test 51-42-50. Harvey to consult with Ryan fire protection due to low numbers. Still needs a full walk through after all heads trimmed out. 1) waiting on updated calcs after backflows were added. 2) need knox fdc plug 3) label riser room door, "riser room" 4) need fire bell installed. 5) min 2" drain needs to be installed due to backflows. currently 1 1/4" 6) still need full sprink final. |