Description:
INSTALL NEW FIRE SPRINKLER SYSTEM THROUGHOUT THE BUILDING & GARAGE.
Contractors:
  • MAXIMUM FIRE PROTECTION L L C ** APA **

Completed Inspections

Permit Status: Final
Permit Number: T17FC00507
Permit Description: INSTALL NEW FIRE SPRINKLER SYSTEM THROUGHOUT THE BUILDING & GARAGE.
Total Completed Inspections - 2
Date Description Inspector Results Comments
11/17/2017 FIRE SPKLR - OH PIPING & HYDRO JPEELDAVIS Approved All areas were completed. Need to add two heads in the NW room bedroom and living room
12/28/2017 FIRE SPKLR - FINAL jvincent Approved PA only on room #102 and the hallway/corridor that serves that room. This was only done so they could get TCO. Main drain test 51-42-50. Harvey to consult with Ryan fire protection due to low numbers. Still needs a full walk through after all heads trimmed out.
1) waiting on updated calcs after backflows were added.
2) need knox fdc plug
3) label riser room door, "riser room"
4) need fire bell installed.
5) min 2" drain needs to be installed due to backflows. currently 1 1/4"
6) still need full sprink final.

Documents

File Name Document Type  
001_SPRINKLER.TIF FIRE PLANS VIEW
002_SPRINKLER.TIF FIRE PLANS VIEW
003_SPRINKLER.TIF FIRE PLANS VIEW
004_SPRINKLER.TIF FIRE PLANS VIEW
005_SPRINKLER.TIF FIRE PLANS VIEW
006_SPRINKLER.TIF FIRE PLANS VIEW
007_SPRINKLER.TIF FIRE PLANS VIEW
008_SPRINKLER.TIF FIRE PLANS VIEW
None DOCUMENTS VIEW