Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit: T17FC00507

Parcel: 11704214A


Addresses:

58 E 5TH ST


Inspection Status: Approved

Inspection History: FIRE SPKLR - FINAL

Permit Number - T17FC00507

Inspection Description - FIRE SPKLR - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
05/10/2018 FIRE SPKLR - FINAL Approved
12/28/2017 FIRE SPKLR - FINAL Partial Approval PA only on room #102 and the hallway/corridor that serves that room. This was only done so they could get TCO. Main drain test 51-42-50. Harvey to consult with Ryan fire protection due to low numbers. Still needs a full walk through after all heads trimmed out.
1) waiting on updated calcs after backflows were added.
2) need knox fdc plug
3) label riser room door, "riser room"
4) need fire bell installed.
5) min 2" drain needs to be installed due to backflows. currently 1 1/4"
6) still need full sprink final.