Inspection History Details
Inspection Status: Approved
Inspection History: FIRE SPKLR - FINAL
Permit Number - T17FC00507
Inspection Description - FIRE SPKLR - FINAL
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/10/2018 | FIRE SPKLR - FINAL | Approved | ||
| 12/28/2017 | FIRE SPKLR - FINAL | Partial Approval | PA only on room #102 and the hallway/corridor that serves that room. This was only done so they could get TCO. Main drain test 51-42-50. Harvey to consult with Ryan fire protection due to low numbers. Still needs a full walk through after all heads trimmed out. 1) waiting on updated calcs after backflows were added. 2) need knox fdc plug 3) label riser room door, "riser room" 4) need fire bell installed. 5) min 2" drain needs to be installed due to backflows. currently 1 1/4" 6) still need full sprink final. |