Permit: T15CM05402
Permit Details
Status:
C of o
Type:
COMMERCIAL ALTERATION
Address:
2700 E EXECUTIVE DR #140
Address NEW:
2700 E EXECUTIVE DR #140
Apply Date:
08/06/2015
Applicant:
STEPHEN LEON MOOS
Description:
WAREHOUSE
Contractors:
- WAID CONSTRUCTION INC
Permit Reviews
Permit Number - T15CM05402
Permit Status: C of o
Permit Description: WAREHOUSE
| Start Date | Submittal | Complete Date | Status |
|---|---|---|---|
| 08/06/2015 | COMMERCIAL - TI | 08/13/2015 | COMPLETED |
| 08/13/2015 | WALK THRU - COMM | 08/13/2015 | COMPLETED |
Outstanding Activity Conditions
Permit Number - T15CM05402
Permit Status: C of o
Permit Description: WAREHOUSE
Total Outstanding Activity Conditions - 1
| Date | Name |
|---|---|
| 08/06/2015 | PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION. |
Completed Inspections
Permit Status: C of o
Permit Number: T15CM05402
Permit Description: WAREHOUSE
Total Completed Inspections - 20
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/24/2015 | PLUMBING - ROUGH, SOIL | TVALENCIA | Approved | 1. DWV WATER TEST OF NEW ROUGH PLUMBING UNDER SLAB APPROVED 2. P.O.C. OF NEW BUILDING DRAIN TO EXISTING BUILDING DRAIN OKAY 3. PERM CAPS OF EXISTING DRAINS OKAY 4. OK TO BACKFILL TRENCH |
| 08/24/2015 | PLUMBING - ROUGH, SOIL | TVALENC1 | Approved | IVRS - Inspection :* |
| 09/02/2015 | PLUMBING - INTERMEDIATE | MRAMBER | Approved | IVRS - Inspection :* |
| 09/02/2015 | ELECTRIC - INTERMEDIATE | MRAMBER | Approved | IVRS - Inspection :* |
| 09/02/2015 | FRAMING | MRAMBER | Approved | IVRS - Inspection :* |
| 09/08/2015 | SHEET ROCK NAILING | MRAMBER | Approved | IVRS - Inspection :* |
| 09/16/2015 | PLUMBING - PROGRESS | TVALENC1 | Approved | IVRS - Inspection :* |
| 09/29/2015 | FIRE - FINAL | nsprenger | Approved | 1. storage on racks in where house is too high - need to limit to 12 feet. Mark a permanent line at the 12 foot mark on all rack storage and place signs stating that no storage is to be over 12 feet high. 2. Painted sprinkler heads in hall between # 130 and #140. 3. Lock on door ( office) with drum storage and boxes of resin plastics. 4. Portable room (booth) over 4 feet in wherehouse ( Needs head dropped into it). |
| 01/05/2016 | FIRE SPKLR - FINAL | nsprenger | Approved | |
| 01/06/2016 | ENGINEERING - FINAL | RLEDONNE | Approved | |
| 01/06/2016 | PLUMBING - ABOVE CEILING | MRAMBER | Approved | |
| 01/06/2016 | PLUMBING - FINAL | MRAMBER | Approved | |
| 01/06/2016 | MECHANICAL - INTERMEDIATE | MRAMBER | Approved | |
| 01/06/2016 | MECHANICAL - ABOVE CEILING | MRAMBER | Approved | |
| 01/06/2016 | MECHANICAL - FINAL | MRAMBER | Approved | |
| 01/06/2016 | ELECTRIC - ABOVE CEILING | MRAMBER | Approved | |
| 01/06/2016 | ELECTRIC - FINAL | MRAMBER | Approved | |
| 01/06/2016 | BUILDING ABOVE CEILING | MRAMBER | Approved | |
| 01/06/2016 | BUILDING - PROGRESS | MRAMBER | Approved | |
| 01/06/2016 | BUILDING - FINAL | MRAMBER | Approved |