Permit: T15CM05402

Parcel: 140420780

Inspection Status: Approved

Inspection History: FIRE - FINAL

Date Description Inspector Results Comments
01/05/2016 FIRE - FINAL Approved
09/29/2015 FIRE - FINAL Denied 1. storage on racks in where house is too high - need to limit to 12 feet. Mark a permanent line at the 12 foot mark on all rack storage and place signs stating that no storage is to be over 12 feet high.
2. Painted sprinkler heads in hall between # 130 and #140.
3. Lock on door ( office) with drum storage and boxes of resin plastics.
4. Portable room (booth) over 4 feet in wherehouse ( Needs head dropped into it).