Inspection History Details
Inspection Status: Approved
Inspection History: FIRE - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/05/2016 | FIRE - FINAL | Approved | ||
| 09/29/2015 | FIRE - FINAL | Denied | 1. storage on racks in where house is too high - need to limit to 12 feet. Mark a permanent line at the 12 foot mark on all rack storage and place signs stating that no storage is to be over 12 feet high. 2. Painted sprinkler heads in hall between # 130 and #140. 3. Lock on door ( office) with drum storage and boxes of resin plastics. 4. Portable room (booth) over 4 feet in wherehouse ( Needs head dropped into it). |