Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T15CM05402
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 08/06/2015 | MICHAEL ST. PAUL | ZONING | REVIEW | Approved | |
| 08/06/2015 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Completed | |
| 08/06/2015 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | #1. Please provide complete panel schedules including load calc's, for all new and existing lighting and power. #2. All lighting and power, including receptacles, equipment to be shown on the floorplans complete with circuit designations. #3.Please provide complete light fixture schedules. #4. Provide IECC compliance for interior lighting. REF; IBC SEC. 107.2.1 |
| 08/06/2015 | PAUL BAUGHMAN | ENGINEERING | REVIEW | Approved | |
| 08/06/2015 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 08/06/2015 | ROBERT SHERRY | WATER | REVIEW | Completed | |
| 08/06/2015 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Completed | |
| 08/06/2015 | MARTIN BROWN | FIRE | REVIEW | Approved | |
| 08/06/2015 | ERIC NEWCOMB | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed |