Permit: T15BU01403
Permit Details
Status:
Final
Type:
SINGLE FAMILY OTHER
Address:
7475 E RIO VISTA CI
Address NEW:
7475 E RIO VISTA CI
Apply Date:
12/04/2015
Applicant:
RAMON FRAGOZO
Description:
SPRINKLER
Contractors:
- UNLIMITED PLUMBING WORKS LLC
Outstanding Activity Conditions
Permit Number - T15BU01403
Permit Status: Final
Permit Description: SPRINKLER
Total Outstanding Activity Conditions - 1
| Date | Name |
|---|---|
| 12/04/2015 | PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION. |
Completed Inspections
Permit Status: Final
Permit Number: T15BU01403
Permit Description: SPRINKLER
Total Completed Inspections - 2
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/21/2015 | FIRE SPKLR - FINAL | nsprenger | Approved | Still have a bedroom with a head that is 12 feet off one wall. Must be 3 feet from center of any fan, 2 feet off any heat registers and no closer to any wall than 4 inches. NO FURTHER OFF A WALL THAN 10 FEET WHEN USING SINGLE HEAD IN A ROOM - PER APPROVED PLANS. Head in entry is angled crooked and must be installed straight to asure proper coverage of area. |
| 12/21/2015 | FIRE SPKLR - OH PIPING & HYDRO | nsprenger | Approved | There is no check valve, flow switch, electric bell or 1/4 inch gauge and 1/2 inch drain valve. System is a D, but there are 5 occupants in this assisted living and the system's flow switch will need to be monitored, with a pull and smoke near an annunciator/control panel interior. Will need seperate alarm permit for installation of monitoring and smoke,flow, pull, control panel installation. |