Inspection Status: Approved
Inspection History: FIRE SPKLR - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/09/2016 | FIRE SPKLR - FINAL | Approved | ||
| 12/21/2015 | FIRE SPKLR - FINAL | Denied | Still have a bedroom with a head that is 12 feet off one wall. Must be 3 feet from center of any fan, 2 feet off any heat registers and no closer to any wall than 4 inches. NO FURTHER OFF A WALL THAN 10 FEET WHEN USING SINGLE HEAD IN A ROOM - PER APPROVED PLANS. Head in entry is angled crooked and must be installed straight to asure proper coverage of area. |
|
| 12/17/2015 | FIRE SPKLR - FINAL | Denied | missing a head in the hall way 12 feet off a wall in kitchen 12 feet off a wall in bedroom straighten a couple of heads out in the bathroom and bedrooms |
|
| 12/14/2015 | FIRE SPKLR - FINAL | Denied | Not ready still installing pipe and hangers, need to check sprinkler coverage inside each room, was advised to insulate all piping. |