Permit: T15BU01403

Parcel: 114470700


Addresses:

7475 E RIO VISTA CI

Inspection Status: Approved

Inspection History: FIRE SPKLR - OH PIPING & HYDRO

Date Description Inspector Results Comments
02/09/2016 FIRE SPKLR - OH PIPING & HYDRO Approved
01/26/2016 FIRE SPKLR - OH PIPING & HYDRO Partial Approval Navarrete on site. They made corrections that nsprenger noted. Still needs the following.
1) Wire bell next to riser and it needs to be tested.
2) Monitoring not needed. 13D system with no control valve. Connected straight to domestic.
12/21/2015 FIRE SPKLR - OH PIPING & HYDRO Denied There is no check valve, flow switch, electric bell or 1/4 inch gauge and 1/2 inch drain valve. System is a D, but there are 5 occupants in this assisted living and the system's flow switch will need to be monitored, with a pull and smoke near an annunciator/control panel interior. Will need seperate alarm permit for installation of monitoring and smoke,flow, pull, control panel installation.
12/17/2015 FIRE SPKLR - OH PIPING & HYDRO Denied can not see hangers on pipe ( insulation on pipe). Mark where hangers are.
12/14/2015 FIRE SPKLR - OH PIPING & HYDRO Denied Not ready still installing pipe and hangers, need to check sprinkler coverage inside each room, was advised to insulate all piping.