Permit: T14BU01383
Permit Details
Apply Date:
12/15/2014
Applicant:
ALLAN FIRE PROTECTION SYSTEMS
Description:
Paint Booth & T.I. 32 new heads
Contractors:
- ALLAN FIRE PROTECTION SYSTEMS
Outstanding Activity Conditions
Permit Number - T14BU01383
Permit Status: Expired
Permit Description: Paint Booth & T.I. 32 new heads
Total Outstanding Activity Conditions - 1
| Date | Name |
|---|---|
| 12/15/2014 | PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION. |
Outstanding Inspections
Permit Status: Expired
Permit Number: T14BU01383
Permite Description: Paint Booth & T.I. 32 new heads
Total Outstanding Inspections - 1
| Last Inspection Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/22/2015 | FIRE SPKLR - FINAL | N/A | Cancelled |
Completed Inspections
Permit Status: Expired
Permit Number: T14BU01383
Permit Description: Paint Booth & T.I. 32 new heads
Total Completed Inspections - 1
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/14/2015 | FIRE SPKLR - OH PIPING & HYDRO | CSCHULTZ | Approved | 200 psi for 2 hours Approved Placement Approved Still needs to be monitored Door separating mixing room and spray paint room shall be self-closing and latching, need to add a sign stating door needs to stay shut at all times. Reason for this is the sprinkler calculations work on all heads at once in the spray booth the head in the mixing room is not part of the calculations if it was the calculations will not work and a possible fire pump will need to be added. |