Inspection History Details
Inspection Status: Approved
Inspection History: FIRE SPKLR - OH PIPING & HYDRO
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/14/2015 | FIRE SPKLR - OH PIPING & HYDRO | Approved | 200 psi for 2 hours Approved Placement Approved Still needs to be monitored Door separating mixing room and spray paint room shall be self-closing and latching, need to add a sign stating door needs to stay shut at all times. Reason for this is the sprinkler calculations work on all heads at once in the spray booth the head in the mixing room is not part of the calculations if it was the calculations will not work and a possible fire pump will need to be added. |