Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Details

Status:
Final
Type:
COMMERCIAL OTHER
Apply Date:
11/18/2014
Applicant:
ALLAN FIRE PROTECTION SYSTEMS
Description:
85' 4" UG & 93 New Heads
Contractors:
  • ALLAN FIRE PROTECTION SYSTEMS

Outstanding Activity Conditions

Permit Number - T14BU01289
Permit Status: Final
Permit Description: 85' 4" UG & 93 New Heads
Total Outstanding Activity Conditions - 1
Date Name
11/18/2014 PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION.

Completed Inspections

Permit Status: Final
Permit Number: T14BU01289
Permit Description: 85' 4" UG & 93 New Heads
Total Completed Inspections - 4
Date Description Inspector Results Comments
12/16/2014 FIRE SPKLR - OH PIPING & HYDRO CBASALDUA Approved
02/06/2015 FIRE SPKLR - UG, PIPING, HYDRO CBASALDUA Approved
02/13/2015 FIRE SPKLR - UG PIPING FLUSH nsprenger Approved On arrival, the 4 Inch main was reduced to a 1 and 3/4 inch double jackets house. They changed to a 4 " Pipe connected to the main and flow test began. Full flow was reached within 30 seconds and water ran clean for at least 5 minutes. Flush on the City side had already been completed yesterday so little sediment was in water to begin with.
Approved, NS 2/ 13 /15
09/15/2015 FIRE SPKLR - FINAL CBASALDUA Approved

Documents

File Name Document Type  
001_SPRINKLER.TIF FIRE PLANS VIEW
002_SPRINKLER.TIF FIRE PLANS VIEW
None DOCUMENTS VIEW