Inspection History: FIRE SPKLR - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/15/2015 | FIRE SPKLR - FINAL | Approved | ||
| 02/17/2015 | FIRE SPKLR - FINAL | Denied | Drain test 82-78-82 Fire bell test 38 sec. 1. Install pressure relief valve on riser 2. Paint outside piping to riser 3. Need UL/FM approved fire alarm monitoring system install |