Permit: T14BU01289

Parcel: 114469490

Inspection Status: Approved

Inspection History: FIRE SPKLR - UG PIPING FLUSH

Permit Number - T14BU01289

Inspection Description - FIRE SPKLR - UG PIPING FLUSH

Inspection Status - Approved

Date Description Inspector Results Comments
02/13/2015 FIRE SPKLR - UG PIPING FLUSH Approved On arrival, the 4 Inch main was reduced to a 1 and 3/4 inch double jackets house. They changed to a 4 " Pipe connected to the main and flow test began. Full flow was reached within 30 seconds and water ran clean for at least 5 minutes. Flush on the City side had already been completed yesterday so little sediment was in water to begin with.
Approved, NS 2/ 13 /15