07/15/2014 MECHANICAL 07/18/2014 COMPLETED Review Details

Outstanding Activity Conditions

Permit Number - T14BU00803
Permit Status: Expired
Permit Description: KITCHEN FIRE SUPPRESSION SYSTEM
Total Outstanding Activity Conditions - 1
Date Name
07/15/2014 PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION.

Outstanding Inspections

Permit Status: Expired
Permit Number: T14BU00803
Permite Description: KITCHEN FIRE SUPPRESSION SYSTEM
Total Outstanding Inspections - 1
Last Inspection Date Description Inspector Results Comments
12/30/2014 FIRE - KITCHEN EXH HOOD FINAL N/A Denied 1)Burner is not under the hood (far right side) all appliances no in correct position as per approved plans
2) Pull station is 61 inches high - must be between 42 inches and 48 inches.
3.) Pull station is 6 feet away from the edge of the hood- must be a minimum of 10 feet away and maximum of 20 feet away
4) Outlet under hood does not have proper faceplate and hole in the tile around it is a break in the fire barrier.
5) No pull was performed - need to do pull test and cut the link on next inspection.

Completed Inspections

Permit Status: Expired
Permit Number: T14BU00803
Permit Description: KITCHEN FIRE SUPPRESSION SYSTEM
Total Completed Inspections - 1
Date Description Inspector Results Comments
08/28/2014 MECHANICAL - FINAL JMILITEL Approved IVRS - Inspection :*

Documents

File Name Document Type  
None DOCUMENTS VIEW
None FIRE PLANS VIEW