Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
Permit Number - T14BU00803
Inspection Description - MECHANICAL - FINAL
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/28/2014 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* | |
| 08/13/2014 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
| 08/13/2014 | MECHANICAL - FINAL | Denied | REPAIR BROKEN ELEC. CONDUITS ON ROOF THE UPPER SECTION OF ALL 3 GREASE DUCTS IS INSTALL WITH SCREWS INSTEAD OF WELDS. PROVIDE WELDED JOINTS AT THESE LOCATIONS. PROVIDE GREAS RECEPTORS AT EACH DRAIN OUTLET ON NS. CONNECT CONFIRM RATED SHAFTS OR FIRE WRAP DUE TO CONCEALED LOCATION | |
| 08/08/2014 | MECHANICAL - FINAL | Not ready for Inspection | IVRS - Inspection :* |