Inspection Status: Denied
Inspection History: FIRE - KITCHEN EXH HOOD FINAL
Permit Number - T14BU00803
Inspection Description - FIRE - KITCHEN EXH HOOD FINAL
Inspection Status - Denied
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/30/2014 | FIRE - KITCHEN EXH HOOD FINAL | Denied | 1)Burner is not under the hood (far right side) all appliances no in correct position as per approved plans 2) Pull station is 61 inches high - must be between 42 inches and 48 inches. 3.) Pull station is 6 feet away from the edge of the hood- must be a minimum of 10 feet away and maximum of 20 feet away 4) Outlet under hood does not have proper faceplate and hole in the tile around it is a break in the fire barrier. 5) No pull was performed - need to do pull test and cut the link on next inspection. |
|
| 12/10/2014 | FIRE - KITCHEN EXH HOOD FINAL | Denied | on site at 11:45 am talked to the owner he stated that Armor left because a screen was missing and the hood testing would not pass. No one from Armor called to cancell |