Permit: T14BU00803

Parcel: 11307087C


Addresses:

3001 N CAMPBELL AV


Inspection Status: Denied

Inspection History: FIRE - KITCHEN EXH HOOD FINAL

Permit Number - T14BU00803

Inspection Description - FIRE - KITCHEN EXH HOOD FINAL

Inspection Status - Denied

Date Description Inspector Results Comments
12/30/2014 FIRE - KITCHEN EXH HOOD FINAL Denied 1)Burner is not under the hood (far right side) all appliances no in correct position as per approved plans
2) Pull station is 61 inches high - must be between 42 inches and 48 inches.
3.) Pull station is 6 feet away from the edge of the hood- must be a minimum of 10 feet away and maximum of 20 feet away
4) Outlet under hood does not have proper faceplate and hole in the tile around it is a break in the fire barrier.
5) No pull was performed - need to do pull test and cut the link on next inspection.
12/10/2014 FIRE - KITCHEN EXH HOOD FINAL Denied on site at 11:45 am talked to the owner he stated that Armor left because a screen was missing and the hood testing would not pass. No one from Armor called to cancell