Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Details

Status:
Closed
Type:
SINGLE FAMILY OTHER
Address NEW:
2914 N FONTANA AV
Apply Date:
04/20/2012
Applicant:
EAST VALLEY DISASTER SERVICES INC
Description:
REPLACE 200 AMP PANEL
Contractors:
  • EAST VALLEY DISASTER SERVICES INC

Permit Reviews

Permit Number - T12CM02117
Permit Status: Closed
Permit Description: REPLACE 200 AMP PANEL
Start Date Submittal Complete Date Status  
05/09/2012 REVISION - - 1ST 05/09/2012 COMPLETED Review Details

Outstanding Activity Conditions

Permit Number - T12CM02117
Permit Status: Closed
Permit Description: REPLACE 200 AMP PANEL
Total Outstanding Activity Conditions - 1
Date Name
04/20/2012 PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION.

Outstanding Inspections

Permit Status: Closed
Permit Number: T12CM02117
Permite Description: REPLACE 200 AMP PANEL
Total Outstanding Inspections - 1
Last Inspection Date Description Inspector Results Comments
05/15/2012 PLUMBING - INTERMEDIATE N/A Partial Approval IVRS - Inspection :*

Completed Inspections

Permit Status: Closed
Permit Number: T12CM02117
Permit Description: REPLACE 200 AMP PANEL
Total Completed Inspections - 5
Date Description Inspector Results Comments
05/07/2012 ELECTRIC - SERVICE UPGRADE JMILITEL Approved IVRS - Inspection :
See detailed listing on site.| 999*
1) CANNOT VERIFY EXISTING GROUNDING
2) PLEASE PROVIDE NEW GROUNDING ELECTRODE SYSTEM
3) PROVIDE A LISTED MAST BRACE KIT
4) PROVIDE A ROOF JACK AT MAST
5) WHAT IS THE OPEN J-B0XN UNDER PANEL FOR ?
6) PLEASE VERIFY PERMIT FOR NEW WIRING INSIDE HOUSE
7) ROMEX DATED 4/18/2012
8) FILL UNUSED OPENINGS IN PANEL
05/17/2012 ELECTRIC - INTERMEDIATE BBENEDON Approved 1. SERVICE BRACING AND GROUNDING TO BE TO CODE
2. PLUMBING IN WALLS OK
3. WIRING IN WALLS OK
08/28/2012 ELECTRIC - FINAL MPUGH Approved IVRS - Inspection :*
08/29/2012 EXCAVATION/LAYOUT REBAR & ZON MPUGH Approved RECON
03/28/2013 TEP CLEARANCE - AM BBENEDON Approved INCR

Documents

File Name Document Type  
None DOCUMENTS VIEW