Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/28/2012 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 08/14/2012 | ELECTRIC - FINAL | Denied | IVRS - Inspection : A reinspection fee has been assessed for this inspection. Multiple inspectio 1) WHERE IS COLLER SWITCH AND THERMOSTAT FOR GAS PACK 2( USE APPROVED HARDWARE FOR DEVICES NOT DRY WALL SCREWS 3) PANEL NOT TO HAVE GENERAL LABELING- TO BE AS PER 408.4 4) FINISH #3,5,6,7 OF PREVIOUS INSPECTION |
|
| 06/13/2012 | ELECTRIC - FINAL | Partial Approval | FINISH ITEMS 2, 3, 5, 6, 7, AND 11 FROM PREVIOUS INSPECTION LIST | |
| 06/01/2012 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) SHEET METAL THREAD SCREWS NOT ALLOWED FOR GROUNDING 250.8 2) CLEAN SURFACE UNDER GROUND BAR 250.12 3) CLEAN EXCESS FOREIGN MATERIAL AND PAINT FROM DEVICE TERMINALS 110.12 4) INSTALL SMOKE DETECTORS PER MANUFACTURES INSTRUCTIONS 5) HOOD NEEDS CONNECTOR AND PROTECT CONDUCTORS 6) BOXES MORE THAN 1/4" BOX TO SURFACE NON COMBUSTIBLES 314.10-USE APPROVED DEVICE-DRYWALL AND TILE 7) PROPERLY GROUND SWITCHES 8) FINISH #3 PREVIOUS INTERMEDIATE INSPECTION (5/14/12) 9) MAST BRACE TO BE LISTED KIT NOT EMT 10) RECEPT COVERS TO BE WEATHER PROOF, WETHER OR NOT PLUGGED INTO 406.8 11) RECEPT IN OUTSIDE LIGHT TO BE GFCI PROTECT 12) NEED OLD WRITE UPS ON SITE |