Permit Number - T12BU00906
Permit Status: Final
Permit Description: Install 859 fire sprinklers
Total Outstanding Activity Conditions - 1
Date Name
07/27/2012 PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION.

Completed Inspections

Permit Status: Final
Permit Number: T12BU00906
Permit Description: Install 859 fire sprinklers
Total Completed Inspections - 4
Date Description Inspector Results Comments
09/27/2012 FIRE SPKLR - FINAL CSCHULTZ Approved Main Contractors permit # T12CM00376
10/29/2012 FIRE SPKLR - UG, PIPING, HYDRO CSCHULTZ Approved Tested for 2 hours at 200 PSI, no leaks noticed all torque mega lug nuts broken off and PVC plastic wrap was around the backside of pipe and ready to wrap all fire sprinkler ductile pipe. Okay to cover with clean dirt.
12/05/2012 FIRE SPKLR - UG PIPING FLUSH CSCHULTZ Approved FLUSHED 1 MIN
02/13/2013 FIRE SPKLR - OH PIPING & HYDRO CSCHULTZ Approved

Documents

File Name Document Type  
001_SPRINKLER.TIF FIRE PLANS VIEW
002_SPRINKLER.TIF FIRE PLANS VIEW
003_SPRINKLER.TIF FIRE PLANS VIEW
004_SPRINKLER.TIF FIRE PLANS VIEW
005_SPRINKLER.TIF FIRE PLANS VIEW
006_SPRINKLER.TIF FIRE PLANS VIEW
007_SPRINKLER.TIF FIRE PLANS VIEW
008_SPRINKLER.TIF FIRE PLANS VIEW
009_SPRINKLER.TIF FIRE PLANS VIEW
None DOCUMENTS VIEW