Inspection History Details
Inspection Status: Approved
Inspection History: FIRE SPKLR - UG, PIPING, HYDRO
Permit Number - T12BU00906
Inspection Description - FIRE SPKLR - UG, PIPING, HYDRO
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
10/29/2012 | FIRE SPKLR - UG, PIPING, HYDRO | Approved | Tested for 2 hours at 200 PSI, no leaks noticed all torque mega lug nuts broken off and PVC plastic wrap was around the backside of pipe and ready to wrap all fire sprinkler ductile pipe. Okay to cover with clean dirt. | |
09/27/2012 | FIRE SPKLR - UG, PIPING, HYDRO | Partial Approval | Okay to bury stub out need 200 PSI for 2hrs when underground is made up with main line. |