Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO.
If you cannot find what you are looking for please
submit a records request.
Inspection Status: Approved
Inspection History: FIRE SPKLR - UG, PIPING, HYDRO
| Date |
Description |
Inspector |
Results |
Comments |
| 10/29/2012 |
FIRE SPKLR - UG, PIPING, HYDRO |
|
Approved |
Tested for 2 hours at 200 PSI, no leaks noticed all torque mega lug nuts broken off and PVC plastic wrap was around the backside of pipe and ready to wrap all fire sprinkler ductile pipe. Okay to cover with clean dirt. |
| 09/27/2012 |
FIRE SPKLR - UG, PIPING, HYDRO |
|
Partial Approval |
Okay to bury stub out need 200 PSI for 2hrs when underground is made up with main line. |