Inspection History: FIRE SPKLR - FINAL
Permit Number - T12BU00906
Inspection Description - FIRE SPKLR - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
05/23/2013 | FIRE SPKLR - FINAL | Approved | ||
05/16/2013 | FIRE SPKLR - FINAL | Cancelled | IVRS - RI canceled | |
05/02/2013 | FIRE SPKLR - FINAL | Cancelled | IVRS - RI canceled | |
02/19/2013 | FIRE SPKLR - FINAL | Partial Approval | Fire pump testing done and passed Label test valve for fire pump with a sign "TEST HEADER or FIRE PUMP TEST HEADER". Need hardware on riser room door exiting to the outside, FD must be able to make entry from the outside. Need to label riser room door with a sign "RISER ROOM". Writing on cal plate needs to be etched on not labeled. Need make up air in fire pump room, damper in ceciling did not open when fire pump testing was completed. |
|
02/13/2013 | FIRE SPKLR - FINAL | Denied | 1. Correct sprinkler coverage by A/C unit # (sales floor) RTU-10 missing sprinkler heads. 2. Remove foil from heads on sprinkler heads by A/C unit RTU-10 check whole line east to west. 3. Foil on sprinkler head next to A/C unit AHU1 4. Uprights need corrected by break room in the warehouse they are 9 feet away from wall. 5. Front storage room by main entrance dripping pipe connections and sprinkler heads. 6. Front storage room by main entrance correct sprinkler coverage head blocked by main steel beam add coverage on south side. 7. Front entrance taped heads 8. Front entrance shopping carts dripping head and taped. 9. Fire pump room is 1 hour fire rated no labels on doors to room showing if they are 20 min fire rated need proof or change doors out. 10. Need hardware on riser room door exiting to the outside, FD must be able to make entry from the outside. 11. Need to label riser room door with a sign "RISER ROOM". |
|
09/27/2012 | FIRE SPKLR - FINAL | Not ready for Inspection | Main Contractors permit # T12CM00376 |