Permit Details

Status:
Final
Type:
COMMERCIAL OTHER
Address:
88 E BROADWAY BL
Apply Date:
05/05/2010
Applicant:
STURGEON ELECTRIC COMPANY
Description:
ELECTRIC:TEMP POWER FOR CONSTRUCTION
Contractors:
  • STURGEON ELECTRIC COMPANY

Permit Reviews

Permit Number - T10EL01046
Permit Status: Final
Permit Description: ELECTRIC:TEMP POWER FOR CONSTRUCTION
Start Date Submittal Complete Date Status  
05/05/2010 ELECTRICAL 05/06/2010 COMPLETED Review Details
05/25/2010 ELECTRICAL 05/25/2010 ACTIVE Review Details

Outstanding Activity Conditions

Permit Number - T10EL01046
Permit Status: Final
Permit Description: ELECTRIC:TEMP POWER FOR CONSTRUCTION
Total Outstanding Activity Conditions - 1
Date Name
05/05/2010 PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION.

Completed Inspections

Permit Status: Final
Permit Number: T10EL01046
Permit Description: ELECTRIC:TEMP POWER FOR CONSTRUCTION
Total Completed Inspections - 7
Date Description Inspector Results Comments
06/10/2010 TEP CLEARANCE - AM JWEATHER Approved TEC CLEARED FOR "TRAILERS ONLY" PER R. HOLLANDER
08/25/2010 ELECTRIC - UNDERGROUND RHOLLAND Approved IVRS - Inspection :*
11/19/2010 ELECTRIC - FINAL RHOLLAND Approved IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
SUN MECHANICAL TRAILER:
1) SUPPORT RACEWAY BELOW MAIN DISCONNECT
2) TIGHTEN LOOSE FITTINGS
3) USE CORRECT SIZED FUSES
4) FILL UNUSED OPENINGS IN PANEL
5) CLEAN SURFACE UNDER GROUND LUG
6) PLEASE PROVIDE PHYSICAL PROTECTION FOR SEAL TITE SES TO XFMR
7) CANNOT STACK LUGS
8) SIZE MAIN BONDING JUMP SIZED INCORRECTLY
9) ONLY ONE CONDUCTOR PER LUG TERMINAL
10) LOOSE TERMINATION FOR CONDUCTOR
11) TRANSFORMER NOT LISTED, PLEASE VERIFY LISTING
12) DO NOT ENERGIZE
12/06/2010 ELECTRIC - TEMP POWER FOR TEST RHOLLAND Approved 1) OK SUN MECHANICAL TRAILER
12/06/2010 ELECTRIC - CONSTRUCTION POWER RHOLLAND Approved IVRS - Inspection :*
12/10/2010 ELECTRIC - TEMPORARY SERVICE RHOLLAND Approved IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1) ONLY ONE CONDUCTOR PER LUG
2) USE APPROVED END CAPS FOR FINE STRANDED CONDUCTORS
3) IDENTIFY PHASES ON CONDUCTORS
05/10/2011 ELECTRIC - UFER LHANLY Approved

Documents

File Name Document Type  
001_E1.TIF CONSTRPLANS VIEW
002_E2.TIF CONSTRPLANS VIEW
None DOCUMENTS VIEW