Permit: T10EL01046
Permit Details
Apply Date:
05/05/2010
Applicant:
STURGEON ELECTRIC COMPANY
Description:
ELECTRIC:TEMP POWER FOR CONSTRUCTION
Contractors:
- STURGEON ELECTRIC COMPANY
Permit Reviews
Permit Number - T10EL01046
Permit Status: Final
Permit Description: ELECTRIC:TEMP POWER FOR CONSTRUCTION
Start Date | Submittal | Complete Date | Status |
---|---|---|---|
05/05/2010 | ELECTRICAL | 05/06/2010 | COMPLETED |
05/25/2010 | ELECTRICAL | 05/25/2010 | ACTIVE |
Outstanding Activity Conditions
Permit Number - T10EL01046
Permit Status: Final
Permit Description: ELECTRIC:TEMP POWER FOR CONSTRUCTION
Total Outstanding Activity Conditions - 1
Date | Name |
---|---|
05/05/2010 | PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION. |
Completed Inspections
Permit Status: Final
Permit Number: T10EL01046
Permit Description: ELECTRIC:TEMP POWER FOR CONSTRUCTION
Total Completed Inspections - 7
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
06/10/2010 | TEP CLEARANCE - AM | JWEATHER | Approved | TEC CLEARED FOR "TRAILERS ONLY" PER R. HOLLANDER |
08/25/2010 | ELECTRIC - UNDERGROUND | RHOLLAND | Approved | IVRS - Inspection :* |
11/19/2010 | ELECTRIC - FINAL | RHOLLAND | Approved | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* SUN MECHANICAL TRAILER: 1) SUPPORT RACEWAY BELOW MAIN DISCONNECT 2) TIGHTEN LOOSE FITTINGS 3) USE CORRECT SIZED FUSES 4) FILL UNUSED OPENINGS IN PANEL 5) CLEAN SURFACE UNDER GROUND LUG 6) PLEASE PROVIDE PHYSICAL PROTECTION FOR SEAL TITE SES TO XFMR 7) CANNOT STACK LUGS 8) SIZE MAIN BONDING JUMP SIZED INCORRECTLY 9) ONLY ONE CONDUCTOR PER LUG TERMINAL 10) LOOSE TERMINATION FOR CONDUCTOR 11) TRANSFORMER NOT LISTED, PLEASE VERIFY LISTING 12) DO NOT ENERGIZE |
12/06/2010 | ELECTRIC - TEMP POWER FOR TEST | RHOLLAND | Approved | 1) OK SUN MECHANICAL TRAILER |
12/06/2010 | ELECTRIC - CONSTRUCTION POWER | RHOLLAND | Approved | IVRS - Inspection :* |
12/10/2010 | ELECTRIC - TEMPORARY SERVICE | RHOLLAND | Approved | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1) ONLY ONE CONDUCTOR PER LUG 2) USE APPROVED END CAPS FOR FINE STRANDED CONDUCTORS 3) IDENTIFY PHASES ON CONDUCTORS |
05/10/2011 | ELECTRIC - UFER | LHANLY | Approved |