Permit: T10EL01046

Parcel: 11717023C


Addresses:

88 E BROADWAY BL


Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T10EL01046

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
05/10/2011 ELECTRIC - FINAL Approved
11/19/2010 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
SUN MECHANICAL TRAILER:
1) SUPPORT RACEWAY BELOW MAIN DISCONNECT
2) TIGHTEN LOOSE FITTINGS
3) USE CORRECT SIZED FUSES
4) FILL UNUSED OPENINGS IN PANEL
5) CLEAN SURFACE UNDER GROUND LUG
6) PLEASE PROVIDE PHYSICAL PROTECTION FOR SEAL TITE SES TO XFMR
7) CANNOT STACK LUGS
8) SIZE MAIN BONDING JUMP SIZED INCORRECTLY
9) ONLY ONE CONDUCTOR PER LUG TERMINAL
10) LOOSE TERMINATION FOR CONDUCTOR
11) TRANSFORMER NOT LISTED, PLEASE VERIFY LISTING
12) DO NOT ENERGIZE
11/05/2010 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
1) TRANSFORMER MAY NOT BE LISTED-INSTALL MISSING LUG FOR GROUNDING CONNECTION
2) SECURE TO PAD
3) PROVIDE GROUNDING ELECTRODE SYSTEMS FOR BOTH TRAILER AND XFMR
06/09/2010 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1) RECEIVED GFI LETTER
2) OK PVC CONDUIT STUS WEST RETAINING WALL
3) INSPECTIONS NEEDED FOR ALL ELECTRICAL EQUIPMENT AND CONNECTIONS
06/04/2010 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1) PROVIDE PROTECTION FOR CONDUCTORS 352.46 & 300.4
2) WILL NEED GFI TEST 230.95
3) NEED LETTER OF TORQUE
4) BOND NEUTRALS AT TRANSFORMERS
5) MAINTAIN SAFE WORKING SPACES 110.26