Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T10EL01046
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
05/10/2011 | ELECTRIC - FINAL | Approved | ||
11/19/2010 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* SUN MECHANICAL TRAILER: 1) SUPPORT RACEWAY BELOW MAIN DISCONNECT 2) TIGHTEN LOOSE FITTINGS 3) USE CORRECT SIZED FUSES 4) FILL UNUSED OPENINGS IN PANEL 5) CLEAN SURFACE UNDER GROUND LUG 6) PLEASE PROVIDE PHYSICAL PROTECTION FOR SEAL TITE SES TO XFMR 7) CANNOT STACK LUGS 8) SIZE MAIN BONDING JUMP SIZED INCORRECTLY 9) ONLY ONE CONDUCTOR PER LUG TERMINAL 10) LOOSE TERMINATION FOR CONDUCTOR 11) TRANSFORMER NOT LISTED, PLEASE VERIFY LISTING 12) DO NOT ENERGIZE |
|
11/05/2010 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1) TRANSFORMER MAY NOT BE LISTED-INSTALL MISSING LUG FOR GROUNDING CONNECTION 2) SECURE TO PAD 3) PROVIDE GROUNDING ELECTRODE SYSTEMS FOR BOTH TRAILER AND XFMR |
|
06/09/2010 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1) RECEIVED GFI LETTER 2) OK PVC CONDUIT STUS WEST RETAINING WALL 3) INSPECTIONS NEEDED FOR ALL ELECTRICAL EQUIPMENT AND CONNECTIONS |
|
06/04/2010 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1) PROVIDE PROTECTION FOR CONDUCTORS 352.46 & 300.4 2) WILL NEED GFI TEST 230.95 3) NEED LETTER OF TORQUE 4) BOND NEUTRALS AT TRANSFORMERS 5) MAINTAIN SAFE WORKING SPACES 110.26 |