Inspection Status: Approved
Inspection History: ELECTRIC - TEMPORARY SERVICE
Permit Number - T10EL01046
Inspection Description - ELECTRIC - TEMPORARY SERVICE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
05/10/2011 | ELECTRIC - TEMPORARY SERVICE | Approved | ||
02/07/2011 | ELECTRIC - TEMPORARY SERVICE | Partial Approval | IVRS - Inspection :* | |
02/04/2011 | ELECTRIC - TEMPORARY SERVICE | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* |
|
12/10/2010 | ELECTRIC - TEMPORARY SERVICE | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1) ONLY ONE CONDUCTOR PER LUG 2) USE APPROVED END CAPS FOR FINE STRANDED CONDUCTORS 3) IDENTIFY PHASES ON CONDUCTORS |
|
12/08/2010 | ELECTRIC - TEMPORARY SERVICE | Partial Approval | IVRS - Inspection :* 1) MAINTAIN WORKING CLEARANCE 2) NEED LOAD CONNECTIONS 3) OK DISCONNECT LINE SIDE AND GROUNDING/BONDING |
|
12/01/2010 | ELECTRIC - TEMPORARY SERVICE | Partial Approval | IVRS - Inspection :* 1) LABEL DISCONNECTS 2) MAINTAINING WORKING SPACE 110.26 3) BONDING JUMPER TO BE CORROSION RESISTANT 250.102 (A) |
|
11/23/2010 | ELECTRIC - TEMPORARY SERVICE | Not ready for Inspection | IVRS - Inspection :* | |
09/08/2010 | ELECTRIC - TEMPORARY SERVICE | Partial Approval | IVRS - Inspection :* 1) OK SPLICES FOR CRANE |
|
09/01/2010 | ELECTRIC - TEMPORARY SERVICE | Partial Approval | IVRS - Inspection :* 1) OK #10 SPLICES 2) FINISH OTHER SPLICES |
|
08/31/2010 | ELECTRIC - TEMPORARY SERVICE | Partial Approval | IVRS - Inspection :* 1) OK GROUNDING ELECTRODE CONDUCTOR TO DISCONNECT 2) OK LABELING OF EQUIPMENT 3) SPLICES STILL NOT INSTALLED |
|
08/27/2010 | ELECTRIC - TEMPORARY SERVICE | Partial Approval | IVRS - Inspection :* 1) ? STRUCTURE DISCONNECT TO HAVE GROUNDING ELECTRODE CONDUCTOR ATTACHED 250.32 (A) & (C) 2) FINISH SPLICES 3) LABEL BREAKER AND DISCONNECT |
|
08/26/2010 | ELECTRIC - TEMPORARY SERVICE | Partial Approval | IVRS - Inspection :* 1) SPLICES TO BE FOR WET LOCATION-SCOTCH KOTE IS LISTED FOR DRY/DAMP, NOT WET 2) GENERATOR TO BE GROUNDED TO GEC |
|
08/25/2010 | ELECTRIC - TEMPORARY SERVICE | Partial Approval | IVRS - Inspection :* 1) OK PULL BOX FOR SPLICING WEST END-NOTE SPLICES TO BE FOR WET LOCATION |
|
06/09/2010 | ELECTRIC - TEMPORARY SERVICE | Partial Approval | IVRS - Inspection :* | |
06/04/2010 | ELECTRIC - TEMPORARY SERVICE | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* |