Permit: T10CM00707
Permit Details
Status:
Expired
Type:
COMMERCIAL OTHER
Address:
657 W SAINT MARYS RD BLDG #2
Address NEW:
657 W SAINT MARYS RD BLDG #2
Apply Date:
03/22/2010
Applicant:
N/A
Description:
REPAIR; STRUCTURAL STORM DAMAGE; T09DV03994
Contractors:
- RIVAS CUSTOM BUILDERS L L C
Permit Reviews
Permit Number - T10CM00707
Permit Status: Expired
Permit Description: REPAIR; STRUCTURAL STORM DAMAGE; T09DV03994
| Start Date | Submittal | Complete Date | Status |
|---|---|---|---|
| 03/22/2010 | COMMERCIAL-BLDG/FIRE/ZONING/ENG | 04/14/2010 | ACTIVE |
Outstanding Activity Conditions
Permit Number - T10CM00707
Permit Status: Expired
Permit Description: REPAIR; STRUCTURAL STORM DAMAGE; T09DV03994
Total Outstanding Activity Conditions - 1
| Date | Name |
|---|---|
| 03/22/2010 | PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION. |
Outstanding Inspections
Permit Status: Expired
Permit Number: T10CM00707
Permite Description: REPAIR; STRUCTURAL STORM DAMAGE; T09DV03994
Total Outstanding Inspections - 2
| Last Inspection Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/19/2010 | FIRE SPKLR - FINAL | N/A | Denied | 1. In building C-8 need alarm bell or water motor gong for sprinkler system. 2. Warehouse #2 riser needs sprinkler inspection done. 3. Need 5yr check valve inspections done on all 4 risers. 4. Need to add sprinkler coverage under lofts in building C-8 building. 5. In C-15 building repair or replace alarm bell for sprinkler system. |
| 05/19/2010 | FIRE - FINAL | N/A | Denied | 1. In building C-8 need plans and permits for lofts that have been added, plans will need structural calculations for lofts. 2. In building C-8 need alarm bell or water motor gong for sprinkler system. 3. Warehouse #2 riser needs sprinkler inspection done. 4. Need 5yr check valve inspections done on all 4 risers. 5. Need to add sprinkler coverage under lofts in building C-8 building. 6. In C-15 building repair or replace alarm bell for sprinkler system. |
Completed Inspections
Permit Status: Expired
Permit Number: T10CM00707
Permit Description: REPAIR; STRUCTURAL STORM DAMAGE; T09DV03994
Total Completed Inspections - 3
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/14/2010 | FRAMING | LHANLY | Approved | |
| 05/14/2010 | EXCAVATION/LAYOUT REBAR & ZON | LHANLY | Approved | |
| 05/20/2010 | BUILDING - FINAL | AQUIROZ | Approved | IVRS - Inspection :* |