Inspection History Details
Inspection Status: Denied
Inspection History: FIRE - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/19/2010 | FIRE - FINAL | Denied | 1. In building C-8 need plans and permits for lofts that have been added, plans will need structural calculations for lofts. 2. In building C-8 need alarm bell or water motor gong for sprinkler system. 3. Warehouse #2 riser needs sprinkler inspection done. 4. Need 5yr check valve inspections done on all 4 risers. 5. Need to add sprinkler coverage under lofts in building C-8 building. 6. In C-15 building repair or replace alarm bell for sprinkler system. |
|