Inspection Status: Denied

Inspection History: FIRE - FINAL

Date Description Inspector Results Comments
05/19/2010 FIRE - FINAL Denied 1. In building C-8 need plans and permits for lofts that have been added, plans will need structural calculations for lofts.
2. In building C-8 need alarm bell or water motor gong for sprinkler system.
3. Warehouse #2 riser needs sprinkler inspection done.
4. Need 5yr check valve inspections done on all 4 risers.
5. Need to add sprinkler coverage under lofts in building C-8 building.
6. In C-15 building repair or replace alarm bell for sprinkler system.
04/27/2010 FIRE - FINAL Denied Not approved 4/27/10
1.) The supporting posts for the beams are missing the 3 1/2 inch bolts fasteners that are required per plans.
2.) Need updated reports for the following:
a.) annual sprinkler inspection
b.) 5 yr. check valve inspection