Inspection Status: Denied

Inspection History: FIRE SPKLR - FINAL

Date Description Inspector Results Comments
05/19/2010 FIRE SPKLR - FINAL Denied 1. In building C-8 need alarm bell or water motor gong for sprinkler system.
2. Warehouse #2 riser needs sprinkler inspection done.
3. Need 5yr check valve inspections done on all 4 risers.
4. Need to add sprinkler coverage under lofts in building C-8 building.
5. In C-15 building repair or replace alarm bell for sprinkler system.