Permit Details

Status:
Expired
Type:
SINGLE FAMILY OTHER
Apply Date:
03/10/2010
Applicant:
N/A
Description:
INST 3TON PACK UNIT
Contractors:
  • S G H AND C L L C

Permit Reviews

Permit Number - T10CM00585
Permit Status: Expired
Permit Description: INST 3TON PACK UNIT
Start Date Submittal Complete Date Status  
03/10/2010 OTHER 03/10/2010 COMPLETED Review Details

Outstanding Activity Conditions

Permit Number - T10CM00585
Permit Status: Expired
Permit Description: INST 3TON PACK UNIT
Total Outstanding Activity Conditions - 1
Date Name
03/10/2010 PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION.

Outstanding Inspections

Permit Status: Expired
Permit Number: T10CM00585
Permite Description: INST 3TON PACK UNIT
Total Outstanding Inspections - 4
Last Inspection Date Description Inspector Results Comments
05/18/2010 ELECTRIC - FINAL N/A Denied IVRS - Inspection :
1. DO NOT USE INDOOR ELECTRICAL FITTINGS OUTDOORS.
2. PROVIDE THE PROPER ROOF JACK AT GAS LINE ON ROOF.
3. A/C UNIT IS OVER-FUSED
4. PROVIDE THE GFCI SERVICE RECEPTACLE
5. PVC IS NOT BLOCKED EVERY 4 FEET
6. EXTERNALLY SEAL ALL DUCT UNDER A/C UNIT
7. GAS LINE NOT HOLDING PRESSURE.
05/18/2010 PLUMBING - GAS PRESSURE TEST N/A Denied IVRS - Inspection :
1. DO NOT USE INDOOR ELECTRICAL FITTINGS OUTDOORS.
2. PROVIDE THE PROPER ROOF JACK AT GAS LINE ON ROOF.
3. A/C UNIT IS OVER-FUSED
4. PROVIDE THE GFCI SERVICE RECEPTACLE
5. PVC IS NOT BLOCKED EVERY 4 FEET
6. EXTERNALLY SEAL ALL DUCT UNDER A/C UNIT
7. GAS LINE NOT HOLDING PRESSURE.
05/18/2010 PLUMBING - FINAL N/A Denied IVRS - Inspection :1. DO NOT USE INDOOR ELECTRICAL FITTINGS OUTDOORS.
2. PROVIDE THE PROPER ROOF JACK AT GAS LINE ON ROOF.
3. A/C UNIT IS OVER-FUSED
4. PROVIDE THE GFCI SERVICE RECEPTACLE
5. PVC IS NOT BLOCKED EVERY 4 FEET
6. EXTERNALLY SEAL ALL DUCT UNDER A/C UNIT
7. GAS LINE NOT HOLDING PRESSURE.See detailed listing on site.| 999*
05/18/2010 MECHANICAL - FINAL N/A Denied IVRS - Inspection :
See detailed listing on site.| 999*