Permit: T10CM00585

Parcel: 133221650

Inspection Status: Denied

Inspection History: PLUMBING - FINAL

Date Description Inspector Results Comments
05/18/2010 PLUMBING - FINAL Denied IVRS - Inspection :1. DO NOT USE INDOOR ELECTRICAL FITTINGS OUTDOORS.
2. PROVIDE THE PROPER ROOF JACK AT GAS LINE ON ROOF.
3. A/C UNIT IS OVER-FUSED
4. PROVIDE THE GFCI SERVICE RECEPTACLE
5. PVC IS NOT BLOCKED EVERY 4 FEET
6. EXTERNALLY SEAL ALL DUCT UNDER A/C UNIT
7. GAS LINE NOT HOLDING PRESSURE.See detailed listing on site.| 999*