Permit: T10CM00585

Parcel: 133221650

Inspection Status: Denied

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
05/18/2010 ELECTRIC - FINAL Denied IVRS - Inspection :
1. DO NOT USE INDOOR ELECTRICAL FITTINGS OUTDOORS.
2. PROVIDE THE PROPER ROOF JACK AT GAS LINE ON ROOF.
3. A/C UNIT IS OVER-FUSED
4. PROVIDE THE GFCI SERVICE RECEPTACLE
5. PVC IS NOT BLOCKED EVERY 4 FEET
6. EXTERNALLY SEAL ALL DUCT UNDER A/C UNIT
7. GAS LINE NOT HOLDING PRESSURE.
04/09/2010 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
1) PROVIDE A 15 POUND PRESSURE GAUGE FOR GAS PRESSURE TEST
2) PROVIDE A ROOF JACK AT GAS LINE PENETRATION
3) SUPPORT CONDENSATE EVERY 4' AND PAINT WITH LATEX PAINT
4) PROVIDE THE REQUIRED GFI SERVICE RECEPT ON THE ROOF
5) FINISH ALL ELECTRICAL WORK