Permit: T09OT02540
Permit Details
Apply Date:
11/24/2009
Applicant:
JOSE LEON
Description:
C OF O: RESTAURANT
Permit Reviews
Permit Number - T09OT02540
Permit Status: C of o
Permit Description: C OF O: RESTAURANT
| Start Date | Submittal | Complete Date | Status |
|---|---|---|---|
| 11/24/2009 | C OF O | 12/01/2009 | COMPLETED |
Completed Inspections
Permit Status: C of o
Permit Number: T09OT02540
Permit Description: C OF O: RESTAURANT
Total Completed Inspections - 2
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/04/2009 | FIRE - FINAL | DRamirez | Approved | Not approved 12/4/09. 1.) Hood (canopy) needs to be inspected by mechanical. Make-up air is attached to system and is not wired to shut off upon activation of system. 2.) Canopy is not sealed. (galvanized steel) 3.) System is of the Dry Powder type. Conferming that TFD policy continues to allow this type system for operations. 4.) Need a "K" type portable fire extinghuisher in the kitchen area. 5.) Remove the slide-bolt from the rear exit door. |
| 12/06/2009 | CERTIFICATE OF OCCUPANCY | MHENSON | Approved | IVRS - Inspection :* 1) INSTALL 15" LETTER FOR ADDRESS 2) WATER HEATER VENT TO GO ABOVE ROOF LINE AND 3/4" TPR VALVE DRAIN 6" TO 12" FROM GROUND 3) INSTALL BACK FLOW PREVENTER ON EXTERIOR HOSE BIBBS 4) NO BARREL BOLTS ON DOORS 5) CAULK TOILETS AT FLOOR 6) NEED FIRE C OF O 7) MECH INSPECTOR TO LOOK AT EXHAUST HOOD |