Inspection History Details
Inspection Status: Approved
Inspection History: CERTIFICATE OF OCCUPANCY
Permit Number - T09OT02540
Inspection Description - CERTIFICATE OF OCCUPANCY
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
07/21/2011 | CERTIFICATE OF OCCUPANCY | Approved | IVRS - Inspection :* | |
07/15/2011 | CERTIFICATE OF OCCUPANCY | Not ready for Inspection | IVRS - Inspection :* 1) NEED FIRE C OF O APPROVED |
|
01/08/2010 | CERTIFICATE OF OCCUPANCY | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) PROVIDE DESIGNED MAKE UP AIR. 2) PROVIDE GILTERS IN HOOD 3) GREASE DUCT IS TO BE WELDED CONTIUOUSLY TO HOOD 4) PROVIDE ACCESS TO AREA ABOVE CEILING 5) PROVIDE ACCESS TO ROOF. 6) PROVIDE GREASE RECEPTOR AT FILTER V-BANK 7) HOOD EXHAUSE 3 MAKE-UP IS TO BE INTERLOCKED TO ONE SWITCH. HOOD CANNOT RUN WITHOUT MVA 8( PROVIDE 16 GA WELDED GREASE DUCT ALL THE WAY TO FAN 9)PROVIDE GREASE RECEPTOR UNDER EXHAUSE FAN 10) PROVIDE EWATHER COVER OVER EXHAUSE FAN MOTOR. |
|
12/06/2009 | CERTIFICATE OF OCCUPANCY | Not ready for Inspection | IVRS - Inspection :* 1) INSTALL 15" LETTER FOR ADDRESS 2) WATER HEATER VENT TO GO ABOVE ROOF LINE AND 3/4" TPR VALVE DRAIN 6" TO 12" FROM GROUND 3) INSTALL BACK FLOW PREVENTER ON EXTERIOR HOSE BIBBS 4) NO BARREL BOLTS ON DOORS 5) CAULK TOILETS AT FLOOR 6) NEED FIRE C OF O 7) MECH INSPECTOR TO LOOK AT EXHAUST HOOD |