Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Approved
Inspection History: FIRE - FINAL
Permit Number - T09OT02540
Inspection Description - FIRE - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
07/18/2011 | FIRE - FINAL | Approved | ||
12/04/2009 | FIRE - FINAL | Denied | Not approved 12/4/09. 1.) Hood (canopy) needs to be inspected by mechanical. Make-up air is attached to system and is not wired to shut off upon activation of system. 2.) Canopy is not sealed. (galvanized steel) 3.) System is of the Dry Powder type. Conferming that TFD policy continues to allow this type system for operations. 4.) Need a "K" type portable fire extinghuisher in the kitchen area. 5.) Remove the slide-bolt from the rear exit door. |