Permit Details

Status:
Expired
Type:
COMMERCIAL OTHER
Address NEW:
9431 E 22ND ST #137
Apply Date:
01/30/2009
Applicant:
CARL SORELL
Description:
C OF O: RESTAURANT SUITES 137 AND 139

Permit Reviews

Permit Number - T09OT00192
Permit Status: Expired
Permit Description: C OF O: RESTAURANT SUITES 137 AND 139
Start Date Submittal Complete Date Status  
01/30/2009 C OF O 01/30/2009 COMPLETED Review Details

Outstanding Inspections

Permit Status: Expired
Permit Number: T09OT00192
Permite Description: C OF O: RESTAURANT SUITES 137 AND 139
Total Outstanding Inspections - 2
Last Inspection Date Description Inspector Results Comments
02/23/2009 FIRE - FINAL N/A Partial Approval TEMP C OF O ONLY. NEED TO INSTALL FIRE EXTINGUISHER SYSTEM TO HOOD FOR CONVEYOR PIZZA OVEN.
02/24/2009 MECHANICAL - HOODS N/A Denied IVRS - Inspection :
See detailed listing on site.| 999*
THE HOOD WOULD MEET TYPE I REQUIREMENTS IF IT HAD A FILTER RACK, 16GA. WELDED DUCT W/2 LAYERS FIRE WRAP,
A TYPE I FAN, FIRE SUPPRESSION SYSTEM, HEAT SENSOR

Completed Inspections

Permit Status: Expired
Permit Number: T09OT00192
Permit Description: C OF O: RESTAURANT SUITES 137 AND 139
Total Completed Inspections - 1
Date Description Inspector Results Comments
02/20/2009 CERTIFICATE OF OCCUPANCY GDABBS Approved IVRS - Inspection :*