Inspection History Details
Inspection Status: Denied
Inspection History: MECHANICAL - HOODS
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/24/2009 | MECHANICAL - HOODS | Denied | IVRS - Inspection : See detailed listing on site.| 999* THE HOOD WOULD MEET TYPE I REQUIREMENTS IF IT HAD A FILTER RACK, 16GA. WELDED DUCT W/2 LAYERS FIRE WRAP, A TYPE I FAN, FIRE SUPPRESSION SYSTEM, HEAT SENSOR |