Permit: T09EL00293
Permit Details
Status:
Expired
Type:
COMMERCIAL OTHER
Address:
4003 E SPEEDWAY BL #119
Address NEW:
4003 E SPEEDWAY BL #119
Apply Date:
02/13/2009
Applicant:
MATT RAMSEY
Description:
UPGRADE: ELECTRIC 600AMP.
Contractors:
- C D W S L L C
Permit Reviews
Permit Number - T09EL00293
Permit Status: Expired
Permit Description: UPGRADE: ELECTRIC 600AMP.
| Start Date | Submittal | Complete Date | Status |
|---|---|---|---|
| 02/13/2009 | ELECTRICAL | 02/17/2009 | COMPLETED |
| 03/05/2010 | ELECTRICAL | 03/05/2010 | COMPLETED |
| 10/14/2009 | ELECTRICAL | 10/14/2009 | COMPLETED |
Outstanding Activity Conditions
Permit Number - T09EL00293
Permit Status: Expired
Permit Description: UPGRADE: ELECTRIC 600AMP.
Total Outstanding Activity Conditions - 1
| Date | Name |
|---|---|
| 02/13/2009 | PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION. |
Outstanding Inspections
Permit Status: Expired
Permit Number: T09EL00293
Permite Description: UPGRADE: ELECTRIC 600AMP.
Total Outstanding Inspections - 4
| Last Inspection Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| ELECTRIC - FINAL | N/A | Not Inspected | ||
| 06/19/2009 | ELECTRIC - UFER | N/A | Partial Approval | IVRS - Inspection :* 1) PROVIDE INFORMATION THAT 800 AMP PLUG RATING FOR BREAKERS IN TRANSFER SWITCH HAVE BEEN INSTALLED 2) NAME PLATE RATING AT TRANSFER SWITCH IS FOR 240V. CANNOT FIELD INSTALL NEW LISTING LABEL FOR NEW 480V RATINGS WITHOUT TESTING LABE ON SITE TO DO FIELD EVALUATION. PROVIDE COPY OF FIELD REPORT. HAVE UL REP CALL ME 3) NEED TO INSTAL PROPER RATED BREAKER ON SECONDARY OF NEW XFMR. HAVE 10 BUISNESS DAYS TO COMPLETE 4) VERIFY WATER AND SPRINKLER PIPING ARE BONDED TO SERVICE 5) PROVIDE PLAQUE AT SERVICE FOR LOCATION OF ON SITE GENERATOR 6) OK TO ENERGIZE EQUIPMENT. RECALL FOR FINAL WHEN READY |
| 09/15/2009 | ELECTRIC - CABLE DROP | N/A | Not ready for Inspection | IVRS - Inspection :* 1) MEETING TO DISCUSS PROJECT 2) COMPLY WITH COMMENTS FROM 6/19/09 3) NEED REVISED AND APPROVED SET OF PLANS FOR ALL CHANGES. WILL NOT ACCEPT LETTER FROM ENGINEER |
| 09/15/2009 | ELECTRIC - SERVICE UPGRADE | N/A | Not ready for Inspection | IVRS - Inspection :* |
Completed Inspections
Permit Status: Expired
Permit Number: T09EL00293
Permit Description: UPGRADE: ELECTRIC 600AMP.
Total Completed Inspections - 1
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/19/2009 | TEP CLEARANCE - AM | JWEATHER | Approved | INCR CLEARED FOR #119 PER R. JIROUDEK |