Inspection History Details
Inspection Status: Partial Approval
Inspection History: ELECTRIC - UFER
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/19/2009 | ELECTRIC - UFER | Partial Approval | IVRS - Inspection :* 1) PROVIDE INFORMATION THAT 800 AMP PLUG RATING FOR BREAKERS IN TRANSFER SWITCH HAVE BEEN INSTALLED 2) NAME PLATE RATING AT TRANSFER SWITCH IS FOR 240V. CANNOT FIELD INSTALL NEW LISTING LABEL FOR NEW 480V RATINGS WITHOUT TESTING LABE ON SITE TO DO FIELD EVALUATION. PROVIDE COPY OF FIELD REPORT. HAVE UL REP CALL ME 3) NEED TO INSTAL PROPER RATED BREAKER ON SECONDARY OF NEW XFMR. HAVE 10 BUISNESS DAYS TO COMPLETE 4) VERIFY WATER AND SPRINKLER PIPING ARE BONDED TO SERVICE 5) PROVIDE PLAQUE AT SERVICE FOR LOCATION OF ON SITE GENERATOR 6) OK TO ENERGIZE EQUIPMENT. RECALL FOR FINAL WHEN READY |
|
| 06/18/2009 | ELECTRIC - UFER | Partial Approval | IVRS - Inspection :* 1) THIS INSPECTION IS TO COVER UP TO SERVICE DISCONNECT OF TRANSFER SWITCH ONLY. ELECTRICAL CONTRACTOR TO LOCK OUT SERVICE DISCONNECT AND NO EQUIPMENT TO BE ENERGIZED WITHOUT. ELECTRICAL INSPECTIONS PERMISSION. CALLED TEP MAP ROOM TO GIVE CLEARANCE 2) RECEIVED CHECK #3114 FOR $150.00 FROM LOGIN, INC. FOR AFTER HOURS INSPECTIONS |