Permit Details

Status:
Final
Type:
COMMERCIAL OTHER
Address:
1415 S CHERRY AV
Apply Date:
12/15/2009
Applicant:
N/A
Description:
REPAIR: CAR INTO BUILDING; T09DV06740
Architects:
  • BOHN, STEPHEN CHARLES
Contractors:
  • BETTER WAY SERVICES INC ,

Permit Reviews

Permit Number - T09CM03292
Permit Status: Final
Permit Description: REPAIR: CAR INTO BUILDING; T09DV06740
Start Date Submittal Complete Date Status  
12/15/2009 COMMERCIAL-BLDG/FIRE/ZONING/ENG 12/15/2009 COMPLETED Review Details

Outstanding Activity Conditions

Permit Number - T09CM03292
Permit Status: Final
Permit Description: REPAIR: CAR INTO BUILDING; T09DV06740
Total Outstanding Activity Conditions - 1
Date Name
12/15/2009 PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION.

Completed Inspections

Permit Status: Final
Permit Number: T09CM03292
Permit Description: REPAIR: CAR INTO BUILDING; T09DV06740
Total Completed Inspections - 12
Date Description Inspector Results Comments
12/28/2009 REINFORCED MASONRY PRE-GROUT MHENSON Approved IVRS - Inspection :*
12/31/2009 MECHANICAL - ABOVE CEILING JMILITEL Approved IVRS - Inspection :*
1) CONNECT RETURN AIR DUCT TO OFFICE AS PER PLANS-WILL CHECK ON FINAL
2) OK FOR CEILING TILES
12/31/2009 BUILDING ABOVE CEILING JBURGE Approved IVRS - Inspection :*
1) OK TO SET CEILING TILES
12/31/2009 ELECTRIC - INTERMEDIATE RHOLLAND Approved IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1) PROTECT M/C CABLE IN WOOD STUDS PER 300.4
2) VDV CABELING TO BE PER 725.3 & 24, 800.3 & 24 AND 300.11
3) FLEX METAL CONDUIT IN BLOCK WALL NOT ALLOWED PER 348.12 (5) & (6)
12/31/2009 ELECTRIC - ABOVE CEILING RHOLLAND Approved IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
01/05/2010 SHEET ROCK NAILING GDABBS Approved IVRS - Inspection :*
01/05/2010 FRAMING GDABBS Approved IVRS - Inspection :*
01/13/2010 MECHANICAL - FINAL MRAMBER Approved IVRS - Inspection :*
01/19/2010 ELECTRIC - FINAL RHOLLAND Approved IVRS - Inspection :*
1) OK ELECTRIC
01/21/2010 FIRE - FINAL DRamirez Approved Approved 1/21/10
01/21/2010 BUILDING - FINAL GDABBS Approved IVRS - Inspection :*
01/22/2010 PERMIT FINALED JWEATHER Approved