Inspection History Details
Inspection Status: Approved
Inspection History: FIRE - FINAL
Permit Number - T09CM03292
Inspection Description - FIRE - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
01/21/2010 | FIRE - FINAL | Approved | Approved 1/21/10 | |
01/14/2010 | FIRE - FINAL | Denied | Not approved 1/13/09 1.) All exterior door and any other door that is on the Exiting Path must be redily openable from the egress side without the use of a key. Replace all keyed turn locks with thumb-turning locks. 2.) Provide a sign on the door between the sales office and the bathroom area that reads, "NOT AN EXIT". 3.) Need a sign over the main enterance (egress side) that reads, "DOOR MUST REMAIN UNLOCKED WHEN THE BUILDING IS OCCUPIED". |