Inspection History: ELECTRIC - INTERMEDIATE

Permit Number - T09CM03292

Inspection Description - ELECTRIC - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
01/19/2010 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*
01/05/2010 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) BLOCK WALL WAS GROUTED-RUNNING ON SURFACE
2) OK POLE BASE
01/04/2010 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) OK FRONT WOOD STUD WALL ONLY
2) ITEMS FOR BLOCK WALL STILL DENIED
12/31/2009 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1) PROTECT M/C CABLE IN WOOD STUDS PER 300.4
2) VDV CABELING TO BE PER 725.3 & 24, 800.3 & 24 AND 300.11
3) FLEX METAL CONDUIT IN BLOCK WALL NOT ALLOWED PER 348.12 (5) & (6)