Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/19/2010 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 01/05/2010 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) BLOCK WALL WAS GROUTED-RUNNING ON SURFACE 2) OK POLE BASE |
|
| 01/04/2010 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) OK FRONT WOOD STUD WALL ONLY 2) ITEMS FOR BLOCK WALL STILL DENIED |
|
| 12/31/2009 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1) PROTECT M/C CABLE IN WOOD STUDS PER 300.4 2) VDV CABELING TO BE PER 725.3 & 24, 800.3 & 24 AND 300.11 3) FLEX METAL CONDUIT IN BLOCK WALL NOT ALLOWED PER 348.12 (5) & (6) |