Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit: T09CM02921
Permit Details
Status:
Final
Type:
COMMERCIAL ADDITION
Address:
5555 S MELPOMENE WY
Address NEW:
5555 S MELPOMENE WY
Apply Date:
11/03/2009
Applicant:
N/A
Description:
ADDITION:2 HORSE BARNS & PIPE CORRAL W/RESTROOMS:UTILITY ROOM AND MECHANICAL
Architects:
- FENECK, JOHN
Contractors:
- CUSTOM BARNS INC
Permit Reviews
Permit Number - T09CM02921
Permit Status: Final
Permit Description: ADDITION:2 HORSE BARNS & PIPE CORRAL W/RESTROOMS:UTILITY ROOM AND MECHANICAL
| Start Date | Submittal | Complete Date | Status |
|---|---|---|---|
| 11/03/2009 | COMMERCIAL-BLDG/FIRE/ZONING/ENG | 12/07/2009 | COMPLETED |
Completed Inspections
Permit Status: Final
Permit Number: T09CM02921
Permit Description: ADDITION:2 HORSE BARNS & PIPE CORRAL W/RESTROOMS:UTILITY ROOM AND MECHANICAL
Total Completed Inspections - 36
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/02/2009 | ELECTRIC - UFER | RJIROUDE | Approved | IVRS - Inspection : See detailed listing on site.| 999* ORIGINAL PERMIT T09EL01123 |
| 07/02/2009 | ELECTRIC - UNDERGROUND | RJIROUDE | Approved | IVRS - Inspection :* 1) OK 2-3" PVC TO ARENA 2) GROUNDING ELECTRODE CONDUCTOR TO CONNECT TO REBAR IN BOTTOM OF FOOTING 3) INSTALL GROUND CLAMP LISTED FOR DIRECT BURY AND FOR USE ON REBAR 4) DO NOT POUR FOOTING UNTIL UFER IS APPROVED ORIGINAL PERMIT T09EL01123 |
| 09/30/2009 | BUILDING PRE-SLAB | GDABBS | Approved | |
| 09/30/2009 | EXCAVATION/LAYOUT REBAR & ZON | GDABBS | Approved | |
| 10/27/2009 | BUILDING - PROGRESS | GDABBS | Approved | 1) 22 EXCAVATIONS 2' X 3' FOR MARE MOTE POLES PARTIAL APPROVAL ON BU #T09BU00695 |
| 12/10/2009 | PLUMBING - ROUGH, SOIL | RLEDONNE | Approved | IVRS - Inspection :* 1) PIPING TO NEW SEPTIC FROM NEW BARR TEST OK 2) YARDWATER TEST OK |
| 12/10/2009 | PLUMBING - YARD WTR LINE/TEST | RLEDONNE | Approved | IVRS - Inspection :* |
| 12/15/2009 | ELECTRIC - INTERMEDIATE | RJIROUDE | Approved | IVRS - Inspection : See detailed listing on site.| 999* 1) GROUNDS AND NEUTRALS TO BE SEPERATE AT PANEL 2) EXPOSE GROUNDING ELECTRODE SYSTEM AT MARE MOTEL 3) GROUNDING ELECTRODE UFER AT BARN WAS DENIED ON 7/2/09 4) REMOVE COVER AT 400 AMP PANEL 5) MARK SERVICE DISCONNECTS AND INDICATE WHAT IS SERVED BY |
| 12/15/2009 | PLUMBING - PRE SLAB | RLEDONNE | Approved | IVRS - Inspection :* |
| 12/15/2009 | ELECTRIC - OUTDOOR LIGHTING | RJIROUDE | Approved | IVRS - Inspection :* |
| 12/15/2009 | ELECTRIC - PROGRESS | RJIROUDE | Approved | IVRS - Inspection : See detailed listing on site.| 999* |
| 12/15/2009 | ELECTRIC - CABLE DROP | RJIROUDE | Approved | IVRS - Inspection : See detailed listing on site.| 999* |
| 12/15/2009 | ELECTRIC - SERVICE RELOCATION | RJIROUDE | Approved | IVRS - Inspection : See detailed listing on site.| 999* |
| 01/07/2010 | TEP CLEARANCE - AM | JWEATHER | Approved | TEC CLEARED PER R. JIROUDEK |
| 06/29/2010 | PLUMBING - INTERMEDIATE | RRICH | Approved | IVRS - Inspection :* |
| 07/02/2010 | PLUMBING - ABOVE CEILING | RLEDONNE | Approved | IVRS - Inspection :* |
| 07/22/2010 | PLUMBING - FINAL | RLEDONNE | Approved | IVRS - Inspection :* |
| 01/25/2013 | FIRE - FINAL | WMOTTO | Approved | |
| 01/25/2013 | FIRE SPKLR - FINAL | WMOTTO | Approved | |
| 01/25/2013 | FIRE SPKLR - UG, PIPING, HYDRO | WMOTTO | Approved | |
| 01/25/2013 | BUILDING - FINAL | SBURGE | Approved | |
| 01/25/2013 | BUILDING - FINAL | JBURGE | Approved | need electric final |
| 01/25/2013 | MECHANICAL - FINAL | JBURGE | Approved | IVRS - Inspection :* |
| 01/25/2013 | MECHANICAL - INTERMEDIATE | JBURGE | Approved | IVRS - Inspection :* |
| 01/25/2013 | ROOF NAILING | JBURGE | Approved | IVRS - Inspection :* |
| 01/25/2013 | EXT METAL CLIPS/EXT SHEATHING | JBURGE | Approved | IVRS - Inspection :* |
| 01/28/2013 | RIGHT OF WAY - FINAL | MCASTRO | Approved | |
| 01/28/2013 | ELECTRIC - TEMP POWER FOR TEST | rmoreno | Approved | per clearance |
| 01/28/2013 | NPPO - FINAL | MRUSSO | Approved | |
| 01/28/2013 | SIGN - FINAL | MRUSSO | Approved | |
| 01/28/2013 | LANDSCAPE - FINAL | MRUSSO | Approved | |
| 01/28/2013 | ENGINEERING - FINAL | MRUSSO | Approved | |
| 02/11/2013 | OUTDOOR LIGHTING FINAL | RMORENO | Approved | |
| 02/11/2013 | ELECTRIC - TEMPORARY SERVICE | RMORENO | Approved | |
| 02/11/2013 | ELECTRIC - ABOVE CEILING | RMORENO | Approved | |
| 02/12/2013 | ELECTRIC - FINAL | RMORENO | Approved | IVRS - Inspection :* |