Permit: T09CM02921

Parcel: 205661060


Addresses:

5555 S MELPOMENE WY


Inspection Status: Approved

Inspection History: ELECTRIC - UNDERGROUND

Permit Number - T09CM02921

Inspection Description - ELECTRIC - UNDERGROUND

Inspection Status - Approved

Date Description Inspector Results Comments
02/11/2013 ELECTRIC - UNDERGROUND Approved
05/18/2010 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
1. OK 1-2" PVC FROM 400 AMP PANEL TO 200 AMP PANEL. NEED TO REVISE PLANS TO REFLECT CHANGES
07/02/2009 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
1) OK 2-3" PVC TO ARENA
2) GROUNDING ELECTRODE CONDUCTOR TO CONNECT TO REBAR IN BOTTOM OF FOOTING
3) INSTALL GROUND CLAMP LISTED FOR DIRECT BURY AND FOR USE ON REBAR
4) DO NOT POUR FOOTING UNTIL UFER IS APPROVED
ORIGINAL PERMIT T09EL01123
05/14/2009 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
1) OK 1-2 1/2 PVC FROM NEW SERVICE TO EXISTING HOUSE
2) OK 1-2 1/2 PVC FROM NEW SERVICE TO EXISTING BARN
3) OK 203" PVC FROM NEW SERVICE TO BOTTOM OF HILL
4) GROUND CLAMPS TO BE LISTED FOR USE ON GROUND RODS AND LISTED & MARKED FOR DIRECT BURY
5) ENSURE PANELS AT BLDGS HAVE MAIN BREAKERS PER PLANS AND NEC 225
6) ALL NEW SERVICES TO BE UNDERGROUND UNLESS WAIVER OBTAINED
ORIGINAL PERMIT WAS T09EL01123