Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - UNDERGROUND
Permit Number - T09CM02921
Inspection Description - ELECTRIC - UNDERGROUND
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/11/2013 | ELECTRIC - UNDERGROUND | Approved | ||
| 05/18/2010 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :* 1. OK 1-2" PVC FROM 400 AMP PANEL TO 200 AMP PANEL. NEED TO REVISE PLANS TO REFLECT CHANGES |
|
| 07/02/2009 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :* 1) OK 2-3" PVC TO ARENA 2) GROUNDING ELECTRODE CONDUCTOR TO CONNECT TO REBAR IN BOTTOM OF FOOTING 3) INSTALL GROUND CLAMP LISTED FOR DIRECT BURY AND FOR USE ON REBAR 4) DO NOT POUR FOOTING UNTIL UFER IS APPROVED ORIGINAL PERMIT T09EL01123 |
|
| 05/14/2009 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :* 1) OK 1-2 1/2 PVC FROM NEW SERVICE TO EXISTING HOUSE 2) OK 1-2 1/2 PVC FROM NEW SERVICE TO EXISTING BARN 3) OK 203" PVC FROM NEW SERVICE TO BOTTOM OF HILL 4) GROUND CLAMPS TO BE LISTED FOR USE ON GROUND RODS AND LISTED & MARKED FOR DIRECT BURY 5) ENSURE PANELS AT BLDGS HAVE MAIN BREAKERS PER PLANS AND NEC 225 6) ALL NEW SERVICES TO BE UNDERGROUND UNLESS WAIVER OBTAINED ORIGINAL PERMIT WAS T09EL01123 |